Hot Work Fire Watch on Oregon Job Sites: 5 Rules

By FireWatch Compliance 路 Reviewed November 2026 路 Not legal advice. Your fire department has final say.

Short answer: Federal OSHA鈥檚 welding rule calls for a fire watcher where more than a minor fire could develop, kept at least 30 minutes after work ends; NFPA 51B (2019 edition and later) calls for at least one hour. Oregon OSHA enforces workplace safety in Oregon, so confirm which rule your project follows.

1. When a fire watcher is required

OSHA 29 CFR 1910.252 requires one where more than a minor fire could develop, such as appreciable combustibles within 35 feet of the work.

2. Move combustibles or guard the other side

Relocate combustibles at least 35 feet away where practical; otherwise post a fire watch on the opposite side of walls and partitions.

3. Equip and train the watcher

An extinguisher on hand, training to use it, and a way to sound the alarm.

4. Stay after the work ends

At least 30 minutes under OSHA; at least one hour under NFPA 51B, plus up to three more hours of monitoring if the permit authorizer requires it.

5. Check permits and contracts

Your fire department, general contractor, or insurer may require a hot work permit or a longer watch.

Need fire watch coverage in Oregon?

馃摓 Call 1-855-876-3473 Request coverage online

Sources: OSHA 29 CFR 1910.252 路 NFPA 51B